VALVE
Military Spec
FIXED IND 4UH 8
-
YES
DESCRIPTION
The FC-2224 Fire Alarm Control panel is a proven, versa
-
tile, two-zone control with space to accommodate an op
-
tional digital communicator. It meets the requirements of
NFPA Standard 72 for Central Station, Protected Premises,
and Remote (DACT) Supervising Station Fire Alarm Sys
-
tems. It is Listed to UL Standard 864, inherently power lim
-
ited and meets all UL transient immunity requirements.
The many features of the FC-2224 control provide a cost
effective approach to systems design, and allow a great de
-
gree of flexibility in one enclosure. These features include
two (2) Class B, Style B initiating circuits and two (2) Class
B, Style Y notification appliance circuits, rated at 1.25 amps
each. Notification appliance circuits can be configured as
silenceable or non-silenceable.
DIP switch programming is used throughout, eliminating
the need for computers and associated software.
A time delay of 30, 60, or 90 seconds is available for
waterflow switches.
The control is housed in a red steel enclosure with a win-
dow offering a view of LEDs displaying the status of vital
functions. The surface mounted enclosure, with its slim ap-
pearance (33/8-inch depth) is designed to blend with any en-
vironment. Space is available for two (2) B-7R batteries.
Supervision of vital components, plug-in modules, func-
tional switches and standby batteries is provided.
The optional digital communicator includes a wide range
of selectable transmission formats to communicate to most
central stations. Other features of the communicator are: A
line-active indicator for each of two phone lines, “Kiss-Off”
signal LED, dual “low telephone voltage detect” circuitry
and programmable event codes per format. The FC-2224 is
programmable for AC power loss delay required for DACT
operation.
An optional serial annunciator driver allows remote alarm
annunciation to as many as four (4) Model FC-2866 remote
annunciators.
Other optional modules include the FC-2880 I/O module
which provides 34 pre-defined open collector outputs that
can be used to drive LEDs or relays.
AGENCY APPROVALS
UL S1869
CSFM Approved
FEATURES
· Inherently Power Limited
· DIP Switch Programming
· Choice of Output Patterns Including
ANSI S3.41
· Programmable Time Delay for
Waterflow Switches
·
Periodic Trouble Reminder
·
Walk Test Feature
·
Optional Digital Communicator with
Multiple Reporting Formats
·
Serial Annunciator Output (Optional)
·
Surface Mount Technology
FC-2224
TWO-ZONE PANEL
CONVENTIONAL FIRE ALARM CONTROL
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
9020-0483/Ver. 1.5
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control In
-
struments, Inc. for their use. Specifications subject to change without notice. © 2000 All Rights Reserved
An ISO 9001 Certified Company
9020-0483 2 of 2
CHARACTERISTICS AND DIMENSIONS
Supervisory current ` .050 amp.
Alarm current .250 amp.
Operating temperature 32 - 120
o
F (0 - 49
o
C)
Relative humidity 85% (non-condensing)
Dimensions 15 1/8”H x 12 13/16” W x 3 3/8” D
(38.4 cm x 33 cm x 8.5 cm)
ORDERING INFORMATION
Part Number Model Description
150-00001 FC-2224 Two-zone Control, 120 VAC
151-00001 FC-2884 Serial Driver Module
151-00003 FC-2880Å Annunciator Driver Module
151-00004 FC-2866Å Remote Zone Annunciator w/reset and silence switches
151-00005 FC-2104 Digital Alarm Communicator Transmitter
151-00019 2190 Cabinet for FC-2104 DACT (optional)
151-00017 5230 Programmer for FC-2104 DACT
151-00018 7860 Cable w/spade lugs for connection
to Telco RJ31X plug. (Optional)
151-00020 Quick connect cable to connect
5230 Programmer to FC-2104 DACT
151-00007 FC-2224PC Replacement PC board
7628 UL Listed EOL resistor
151-00011 120 VAC Transformer (replacement)
151-00012 230 VAC, 50 Hz Transformer (optional)
Å Requires one (1) FC-2884
FC-2104 DACT reporting formats are:
SIA 8 or 20
SK 3/1 1,400 or 2,300 Hz
Contact ID
SK 4/2
BFSK 1,400 or 2,300 Hz
FC-2880 Annunciator Driver
Module
FC-2866 Remote Zone
Annunciator
FC-2104 Digital Alarm
Communicator Transmitter
FC-2884 Serial Driver Module

NXP USA Inc.
IC GATE DRVR HALF-BRIDGE 32SOIC
Analog Devices Inc.
IC LNR REG CTRLR 2OUT 16SOIC
Nexperia
PBSS4021NT Series 20 V 4.3 A NPN Low VCEsat (BISS) Transistor - SOT-23
Nexperia
PBSS302NZ Series 20 V 5.8 A 1.7 W SMT NPN Low VCEsat (BISS) Transistor - SOT-223
onsemi
FJV42 Series 350 V 500 mA Surface Mount NPN High Voltage Transistor - SOT-23-3
Nexperia
BC846 Series 65 V 100 mA Double NPN General Purpose Transistor - SOT-363
Vishay
GLL4742 Series 1 W 12 V 5 % Tolerance Surface Mount Zener Diode - MELF
Central Semiconductor
Diode Zener Single 15V 5% 350mW 3-Pin SOT-23 T/R
Nexperia
Not Applicable
Microchip
1N496XUS Series 27 V 5 W 1 A Surface Mount Sealed Glass Zener Diode - D5B
Microchip
Jan spec Diode
Vishay
1N4764A Series 1.3 W 100 V 200 mA 5 % Tolerance Through Hole Zener Diode - DO-41
Diodes Incorporated
BZT52C6V8 Series 200 mW 6.8 V 10 mA Surface Mount Zener Diode - SOD-323
Vishay
S4PM Series 1 kV 4 A Surface Mount Glass Passivated Rectifier - TO-277A
Vishay
1N4004GP Series 400 V 30 A Glass Passivated Junction Rectifier - DO-204AL
Vishay
Rectifiers 30A 600V Ultrafast 45ns
Laird Performance Materials
Ferrite Clamp On Cores CLAMP-ON FILTER WHT 250ohms 100MHz
TELEDYNE
TERM TEST POINT SLOTTED .032"DIA
Military Spec
FIXED IND 4UH 8A 12 MOHM TH
关闭
Inquiry
captcha

15815509278

295144934@qq.com
0